Characteristics:
The output circuit all utilizes optic-electrical insulation, resulting in strong resistance to interference.
Economical and practical, versatile, can be achieved up to 96 routes polling survey with unified alarm
Use high-intelligence chip, well self-compensate and self-correction function.
Profile:
CIM21 extended type can select and use 96 routes patrol alarm at most, the input signals include thermocouple,hot resistance and other standard signals. It is easy to use, stable and reliable.
The input outlets of the instrument all have multiple signals and single-channel input capability. Various signals can
be input through each channel simultaneously. The transformation of input signals can be accomplished by simple
selection on the instrument menu, which leads to the easy transformation among different signals (a variety of
thermocouple, thermal resistance, standard voltage/ standard current), enhancing the instrument's commonality
and reliability.
There are two ways of controlled outputs: every channel unified alarm output/ transmission output, and every channel
respectively independent alarm output/ transmission output. Unified alarm includes memory model and the non-memory
model. The output circuit all utilizes optic-electrical insulation, resulting in strong resistance to interference.
It has high brightness LED digital display and all-Chinese big screen LCD display. It's able to connect serial interface.
The instrument uses the embedded structure which makes the installation conveniently.
Main technical parameter:
Product Standard Table:
Num
|
Configuration type
|
Configuration name
|
1
|
Display type
|
LED
digital display
|
2
|
Communication
|
No
|
3
|
Working voltage
|
220VAC
|
Particular Requirements for Product List
Code
|
Configuration type
|
Configuration name
|
T11
|
|
LCD display
|
T21
|
|
RS485
|
T31
|
|
24VDC
|
T41
|
Alarming output
|
Memory type
|
T42
|
|
|
T51
|
Breakage maintain
|
Have
|
T00
|
Special requires
|
Pls list photos
|
Perambulatable input signal
|
Thermocouple K, T, E, B, S; hot resistance G, Cu50, Pt100 (BA1, BA2)
Standard signal 0~10mA, 4~20mA, 0~5V, etc
|
Detection component
connection method
|
Two-wire type, three-wire type
|
Max polling points
|
96 points
|
Effective measuring range
|
10: Pt100 (-200~650℃); 11: Pt100.1 (-99.99~199.99℃)
50: Cu50 (-50~150℃); 42: 4~20mA; 15: 1~5V; 06: full-function input
|
Resolution
|
When the range is -99.9~200.0℃, the resolution is last digit word, just like 0.1.
When the range is -99.9~400.0℃, the resolution is last digit word, just like 0.5.
When the range is more than 400℃, the resolution is last digit word, just like 1.
|
Indication error
|
±0.5%FS, FS is instrument output range
|
Alarm control class
|
The same as indication error.
|
Tour display rate
|
1~10s adjustable
|
Working way
|
Have tour gauging, tour showing; location survey, location showing;
Manually select the point, max tour gauging display, etc.
|
Alarm contact output capacity
|
3A/ 220VAC
|
Power consumption
|
≤12W
|
Environment
|
Environmental temperature:0~45℃ air, relative humidity≤85%; the ambient air
do not contain corrosive gas
|
Dimensions
|
160(height)×80(width)×250(depth)mm
|
Installation dimensions
|
Panel embedded installation, the hole size:153(width)×77(height)mm
|
|